| A. GENERAL
700-1. Scope.
Emergency systems are intended to automatically supply illumination or
power, or both, to designated areas and equipment in the event of failure
of the normal supply or in the event of accident to elements of a system
intended to supply, distribute, and control power and illumination
essential for safety to human life.
700-3. Equipment Approval.
All equipment shall be approved for use on emergency systems.
700-4. Tests and Maintenance.
(a) Conduct or Witness Test.
The authority having jurisdiction shall conduct or witness a test on the
complete system upon installation and periodically afterward.
(b) Tested Periodically.
Systems shall be tested periodically on a schedule acceptable to the
authority having jurisdiction to assure their maintenance in proper
operating condition.
(c) Battery Systems Maintenance.
Where battery systems or unit equipment are involved...the authority
having jurisdiction shall require periodic maintenance.
(d) Written Record.
A written record shall be kept of such tests and maintenance.
(e) Testing Under Load.
Means for testing all emergency lighting and power systems during maximum
anticipated load conditions shall be provided.
700-5. Capacity.
(a) Capacity and Rating.
An emergency system shall have adequate capacity and rating for all loads
to be operated simultaneously. The emergency system shall be suitable for
the maximum available fault current at its terminals.
B. CIRCUIT WIRING
700-9. Wiring, Emergency System.
(b) Wiring.
Wiring from emergency source or emergency source distribution overcurrent
protection to emergency loads shall be kept entirely independent of all
other wiring and equipment and shall not enter the same raceway, cable,
box, or cabinet with other wiring.
Exception No. 1: In transfer equipment enclosures.
Exception No. 2: In exit or emergency lighting fixtures supplied from
two sources.
Exception No. 3: In a common junction box attached to exit or emergency
lighting fixtures supplied from two sources.
Exception No. 4: Wiring of two or more emergency circuits supplied from
the same source shall be permitted in the same raceway, cable, box, or
cabinet.
Exception No. 5: In a common junction box attached to a unit equipment,
and that contains only the branch circuit supplying the unit equipment and
the emergency circuit supply by the unit equipment.
C. SOURCES OF POWER
700-12. General Requirements.
Current supply shall be such that, in the event of failure of the
normal supply to, or within, the building...emergency lighting, emergency
power, or both will be available within the time required for the
application, but not to exceed 10 seconds.
(a) Storage Battery.
Storage batteries used as source of power for emergency systems shall be
of suitable rating and capacity to supply and maintain the total load for
a period of 1-1/2 hours minimum, without the voltage applied to the load
falling below 87-1/2 percent of normal.
Batteries...shall be designed and constructed to meet the requirements
of emergency service and shall be compatible with the charger for that
particular installation.
For a sealed battery, the container shall not be required to be
transparent. However, for the lead acid battery that requires water
additions, transparent or translucent jars shall be furnished.
Automotive-type batteries shall not be used.
An automatic battery charging means shall be provided.
(e) Unit Equipment.
Individual unit equipment for emergency illumination shall consist of (1)
a rechargeable battery; (2) a battery charging means; (3) provisions for
one or more lamps mounted on the equipment, or shall be permitted to have
terminals for remote lamps, or both; and (4) a relaying device arranged to
energize the lamps automatically upon failure of the supply to the unit
equipment. The batteries shall be of suitable rating and capacity to
supply and maintain at not less than 87-1/2 percent of the nominal battery
voltage for the total lamp load associated with the unit for a period of
at least 1-1/2 hours...
Unit equipment shall be permanently mounted in place (i.e., not
portable) and shall have all wiring to each unit installed in accordance
with the requirements of any of the wiring methods in Chapter 3. Flexible
cord- and plug-connection shall be permitted, provided that the cord does
not exceed 3 feet...in length. The branch circuit feeding the unit
equipment shall be the same branch circuit as that serving the normal
lighting in the area and connected ahead of any local switches...
D. EMERGENCY SYSTEM CIRCUITS FOR LIGHTING & POWER
700-15. Loads on Emergency Branch Circuits.
No appliances and no lamps, other than those specified as required for
emergency use, shall be supplied by emergency lighting circuits.
700-16. Emergency Illumination.
Emergency illumination shall include all required means of egress
lighting, illuminated exit signs, and all other lights specified as
necessary to provide required illumination.
Emergency lighting systems shall be so designed and installed that the
failure of any individual lighting element, such as the burning out of a
light bulb, cannot leave in total darkness any space that requires
emergency illumination.
Where high-intensity discharge lighting such as high- and low-pressure
sodium, mercury vapor, and metal halide is used as the sole source of
normal illumination, the emergency lighting system shall be required to
operate until normal illumination has been restored.
|